2000.35.010
This temperature transmitter for DIN/B head converts a signal acquired via PT100, PT1000, Ni100 probes or thermocouple into a current signal for 4..20mA loop (2-wire technology).
Unique features is the programming via NFC technology, not requiring the devices to be powered up. User can chose between a dedicated NFC programmer and RF-Programmer software on Pc or App MyPixsys on smartphone available on Play Store.
2000.35.010 RFID CONVERTER RTD -4..20MA RTD version
€55.51
Tax included
FEATURES
Dimensions | Ø45 mm, 23mm |
---|---|
Power supply | Loop Power (2 wires connection) operating range 6-32 Vdc |
Operating conditions | Temperature -40..85 °C, Humidity 30..90 RH% |
Material | Nylon (PA66) |
Weight | Approx. 30g |
Response time | 600mS (sampling 300mS) |
Sealing | Box and terminal blocks: IP20 |
According to | CE, UL |
Analog inputs | 1 x selectable among Thermoresistances PT100, PT1000, Ni100 - 2/3/4 wires |
Data Logger Function | Sampling time 1..3600 S - 2800 damplings - circular buffer |
Control algorithms | ON - OFF with hysteresis, P., P.I., P.I.D., P.D. time proportional |
Tuning | Manual or automatic |
Alarm mode | Absolute / Threshold, Band, High / Low deviation. Alarm with optional Manual reset. Loop Break Alarm |
Double P.I.D. | Heating / Cooling with dual P.I.D. |
Soft-Start | Rising gradient programmable as Degree / Hour or fixed output % |
Open/Close logics | Open / Close logic for motorized valves |
Software parameter configuration | Memory Card, software LABSOFTVIEW, EASY-UP codes - Programming via APP (NFC) "MyPixsys" for Android and iOS devices |
Rejection | 50-60Hz |
Output resolution | 2 μA |
Max. transmission error | 0,1% f.s or 0,2°C |
Cable resistance | Max 20Ω |
Over range output | f.s. + 5°C |
Under range output | f.s. - 5°C |
Error output | Selectable between 21,5mA or 3,8mA |
Current output protection | 30mA |