STR561 indicator with strain-gauge input is designed as a display for load cells and Melt pressure transducers (mV/V) and includes isolated power supply for the strain-gauge.
Conversion frequency programmable up to 1.2 KHz and resolution up to 24bit ensure high accuracy.
Different analog input calibration modes are selectable (sample weight, percent full-scale value, mV/V value).
Software features worth mentioning include multiple options for Tare management, Totalizer , Sum functions, process trend display with programmable time base or bar-graph with alarm/event thresholds.
An auto-configuration mode has also been implemented for some Dynisco Melt transducers, simplifying the settings required of the user.
Connectivity is provided by RS485 standard with Modbus RTU/Slave protocol.
STR561 interface is also quickly configurable via NFC with MyPixsys APP, without the need to power up the instrument or via multi-language text menus from the frontal keypad
STR561-12ABC-T128R STRAIN GAUGE INDICATOR 96X48RFID OLED 128x64 -2 RL-RS485-128 DEV.-24/230V
FEATURES
Dimensions | 96x48 (Frontale) x 48 mm (1/8Din) |
---|---|
Power supply | 24..230V AC/DC ±15% 50/60 Hz - galvanic isolation 2,5KV |
Consumption | 8 Watt/VA |
Operating conditions | Temperature 0..45 °C, humidity 35..95 RH% (non-condensing), max 2000m a.s.l. |
Material | Box: polycarbonate V0. Front cover: silicone rubber |
Weight | Approx. 165g |
Sealing | Front panel: IP54, Box and terminal blocks: IP20 |
According to | CE, UL |
Analog inputs | 1x 16bit, K,S,R,J,T,E,N,B (comp. -25..85°C, Tol. @25°±0,2% F.S. ±1 digit F.S.), PT100, PT500, PT1000, Ni100, PTC 1K, NTC 10K (B3435K), 0..1/5/10V, 0-20/4..20mA, 0..60 mV, potentiometer 1..150KΩ |
Sampling time | Programmable up to 4,1ms (from 4,12Hz up to 242Hz frequency) |
Auxiliary output | 12/24 VDC - 25mA max for sensor power supply |
Relais outputs | 2 x 2A - 250V AC resistive loads |
Digital inputs | 2 x PNP |
Serial communication | RS485 (1200..115200 Baud) galvanically isolated |
USB | 1 x microUSB (for programming via LabSoftView software) |
Analogue outputs | 1x 0/4..20mA (60000 points) + 1x 5VDC - 35mA max (strain gauge supply) |