Indicator / panel meter STR551  is designed for process acquisition and retransmission via analogue output.

The monochrome OLED graphical display supports process trend displays with programmable sampling time and bar-graph representation with thresholds typically used for level, flow and dosage measurements.

Analogue input is configurable by parameter for a wide range of temperature sensors and process signals in mA and volts. Linearization is customizable up to a maximum of 16 points, useful on irregularly profiled tanks.

Process-related mathematical functions such as Totalizer and Sum are also implemented.

Connectivity is provided by standard RS485 with Modbus RTU/Slave protocol.

For maximum flexibility of use, there is also a choice of horizontal or vertical installation. 

User can program the device using the intuitive interface with multi-language text menus of the MyPixsys App thanks to integrated NFC communication.

STR551-12ABC-T128R DOUBLE SETPOINT INDICATOR 96X48 RFID OLED 128x64 -2 RL-RS485-24/230

€358.68
Tax included

FEATURES

Dimensions 96x48 (Front panel) x 48 mm (1/8Din)
Power supply 24..230V AC/DC ±15% 50/60 Hz - galvanic isolation 2,5KV
Consumption 8 Watt/VA
Operating conditions Temperature 0..45 °C, humidity 35..95 RH% (non-condensing), max 2000m a.s.l.
Material Box: polycarbonate V0. Front cover: silicone rubber
Weight Approx. 165g
Sealing Front panel: IP54, Box and terminal blocks: IP20
According to CE, UL
Analog inputs 1x 16bit, K,S,R,J,T,E,N,B (comp. -25..85°C, Tol. @25°±0,2% F.S. ±1 digit F.S.), PT100, PT500, PT1000, Ni100, PTC 1K, NTC 10K (B3435K), 0..1/5/10V, 0-20/4..20mA, 0..60 mV, potentiometer 1..150KΩ
Sampling time Programmable up to 4,1ms (from 4,12Hz up to 242Hz frequency)
Auxiliary output 12/24 VDC - 25mA max for sensor power supply
Relais outputs 2 x 2A - 250V AC resistive loads
Digital inputs 2 x PNP
Serial communication RS485 (1200..115200 Baud) galvanically isolated
USB 1 x microUSB (for programming via LabSoftView software)
Analogue outputs 1x 0..10V (60000 points) + 1x 0/4..20mA (60000 points)