ATR264 is a programmer dedicated to the automation of small industrial ovens or laboratory ovens, dryers, heat treatment systems, and in general the management of a process involving cycles/profiles with control of the process variable in relation to time.
ATR264 allows the programming of 15 cycles/profiles, each one including up to 30 steps/segments, all free configurable by the user as ramp/soak/cooling.
The device integrates software functions typically required in oven/furnace management: Waiting (in the case the process is delayed in comparison to programmed setpoint) and Cycle Recovery mode (after any power failure).
Like other Pixsys programmers, ATR264 stands out for user-friendly interface and programming mode even for inexperienced operators.
Parameter configuration and cycle programming is possible via MyPixsys App on smartphone thanks to NFC/Rfid technology or on PC with MyPixsysLab software as well as directly from keyboard.
ATR264-12ABC-T PROGRAMMATORE 15 CICLI 48X48 4+5 Digit 1AI-1AO-2DI/O-2RL-RS485
FEATURES
Dimensions | 48x48x80mm |
---|---|
Power supply | 24..230V AC/DC ±15% 50/60 Hz - galvanic isolation 2,5KV |
Consumption | 9 Watt/VA |
Operating conditions | Temperature 0..45 °C, humidity 35..95 RH% (non-condensing), max 2000m a.s.l. |
Material | Box: PC UL94V2 self-extinguishing, front panel: PC UL94V2 |
Weight | Approx. 250g |
Sealing | Front panel: IP65, Box and terminal blocks: IP20 |
According to | CE, UL (-12ABC-T only) |
Analog inputs | 1x 16bit, K,S,R,J,T,E,N,B (comp. -25..85°C, Tol. @25°±0,2% F.S. ±1 digit F.S.), PT100, PT500, PT1000, Ni100, PTC 1K, NTC 10K (B3435K), 0..1/5/10V, 0-20/4..20mA, 0..60 mV, potentiometer 1..150KΩ |
Digital outputs | 2 x PNP 12VDC - 25mA o 24VDC - 15mA selectable by parameter |
Relais outputs | 2 x 2A - 250V AC resistive loads |
Control algorithms | ON - OFF with hysteresis, P., P.I., P.I.D., P.D. time proportional |
Tuning | Manual or automatic |
Alarm mode | Absolute / Threshold, Band, High / Low deviation. Alarm with optional Manual reset. Loop Break Alarm |
Double P.I.D. | Heating / Cooling with dual P.I.D. |
Open/Close logics | Open / Close logic for motorized valves |
Software parameter configuration | Software MyPixsysLab, App MyPixsys |
Digital inputs | 2 x PNP |
Serial communication | RS485 (1200..115200 Baud) galvanically isolated |
Analogue outputs | 1 x 4..20mA (40000 points ± 0,2% F.S ) or 0..10VDC (40000 points ± 0,2% F.S.) |
Cycles / Profiles | up to 15 |
Steps / Segments | up to 30 for each cycle ( max duration per step 99.59 hh.mm) |