ATR224-12ABC CONTROLLER MULTI-SETPOINT

Precedente
Successivo
ATR224-12ABC

PID Controller ATR224 is a simplified and reduced version of the ATR244 series.

The input is programmable for temperature sensors (resistance thermometers and thermocouples), or for mA/Volt current/voltage process signals, often used for pressure transmitters, humidity and flow sensors, or inverters.

Controller outputs are selectable as command and multiple alarm modes (band, deviation...)

The extended range power supply from 24 to 230V AC/DC increases its flexibility.

It is supported by MyPixsys App for configuration via NFC/RFID.

ATR224-12ABC CONTROLLER MULTI-SETPOINT 4+5 digit 1AI-1DI-1DO-2 RELAYS

€159.82
Tax included

FEATURES

Dimensions 48x48x105mm
Power supply 24..230V AC/DC ±15% 50/60 Hz - galvanic isolation 2,5KV
Consumption 8 Watt/VA
Operating conditions Temperature 0..45 °C, humidity 35..95 RH% (non-condensing), max 2000m a.s.l.
Front panel 48 x 48mm
Material Box: PC UL94V2 self-extinguishing, front panel: PC UL94V2
Weight Approx. 185g.
Sealing Front panel: IP65, Box and terminal blocks: IP20
According to CE
Analog inputs 1x 16bit, K,S,R,J,T,N,B (autom. comp. of cold joint -25..85°C, ±0,2% F.S. ±1 digit F.S.), PT100, PT500, PT1000, Ni100, PTC1K, NTC10K (B3435K), 0..10 V, 0/4..20mA, 0..60 mV, Potentiometers 1..150KΩ
Sampling time Programmable up to 2,1ms (frequency up to 470Hz)
Digital outputs 1x SSR 12 / 24 V DC - 25 mA max
Auxiliary output 12/24 VDC - 30mA max for sensor supply
Relais outputs 2 x 2A - 250V AC resistive loads
Control algorithms ON - OFF with hysteresis, P., P.I., P.I.D., P.D. time proportional
Tuning Manual or automatic
Alarm mode Absolute / Threshold, Band, High / Low deviation. Alarm with optional Manual reset. Loop Break Alarm
Soft-Start Rising gradient programmable as Degree / Hour or fixed output %
Open/Close logics Open / Close logic for motorized valves
Software parameter configuration Memory Card, software LABSOFTVIEW, EASY-UP codes - Programming via APP (NFC) "MyPixsys" for Android and iOS devices
Digital inputs 1x PNP
USB 1 x microUSB (for programming via LabSoftView software)