DRR224-12ABC
PID Controller DRR224 PID is a simplified and scaled-down version of the DRR244 series.
The analogue input is programmable for temperature sensors (resistance thermometers and thermocouples), or for mA/Volt current/voltage process signals, which are used by pressure transmitters, humidity and flow sensors, or inverters.
Controller outputs are selectable as command and multiple alarm modes.
The extended range power supply from 24 to 230V AC/DC increases its flexibility.
It is supported by the MyPixsys App for configuration via NFC/RFID.
DRR224-12ABC DIN RAIL CONTROLLER MULTI-SETPOINT 4+5 digit 1AI-1DI-1DO-2 RELAYS
€192.15
Tax included
FEATURES
Dimensions | 71x90x64mm - 4 x DIN43880 modules |
---|---|
Power supply | 24..230V AC/DC ±15% 50/60 Hz - galvanic isolation 2,5KV |
Consumption | 8 Watt/VA |
Operating conditions | Temperature 0..45 °C, humidity 35..95 RH% (non-condensing), max 2000m a.s.l. |
Material | Box: PC UL94V2 self-extinguishing, front panel: PC UL94V2 |
Weight | Approx. 185g |
Sealing | Front panel: IP65, Box and terminal blocks: IP20 |
According to | CE |
Analog inputs | 1x 16bit, K,S,R,J,T,N,B (autom. comp. of cold joint -25..85°C, ±0,2% F.S. ±1 digit F.S.), PT100, PT500, PT1000, Ni100, PTC1K, NTC10K (B3435K), 0..10 V, 0/4..20mA, 0..60 mV, Potentiometers 1..150KΩ |
Sampling time | Programmable up to 2,1ms (frequency up to 470Hz) |
Digital outputs | 1x SSR 12 / 24 V DC - 25 mA max |
Auxiliary output | 12/24 VDC - 30mA max for sensor supply |
Relais outputs | 2 x 2A - 250V AC resistive loads |
Control algorithms | ON - OFF with hysteresis, P., P.I., P.I.D., P.D. time proportional |
Tuning | Manual or automatic |
Alarm mode | Absolute / Threshold, Band, High / Low deviation. Alarm with optional Manual reset. Loop Break Alarm |
Double P.I.D. | Heating / Cooling with dual P.I.D. |
Soft-Start | Rising gradient programmable as Degree / Hour or fixed output % |
Open/Close logics | Open / Close logic for motorized valves |
Software parameter configuration | Memory Card, software LABSOFTVIEW, EASY-UP codes - Programming via APP (NFC) "MyPixsys" for Android and iOS devices |
Digital inputs | 1x PNP |
USB | 1 x microUSB (for programming via MyPixsysLab software) |