ATR464 is a programmer dedicated to the automation of industrial ovens or laboratory ovens, dryers, heat treatment systems, and in general the management of a process involving cycles/profiles with control of the process variable in relation to time.
ATR464 allows the programming of 15 cycles/profiles, each one including up to 30 steps/segments, all free configurable by the user as ramp/soak/cooling.
The device integrates software functions typically required in oven/furnace management: Waiting (in the case the process is delayed in comparison to programmed setpoint) and Cycle Recovery mode (after any power failure).
Like other Pixsys programmers, ATR464 stands out for user-friendly interface and programming mode even for inexperienced operators.
Parameter configuration and cycle programming is possible via MyPixsys App on smartphone thanks to NFC/Rfid technology or on PC with MyPixsysLab software as well as directly from keyboard.
PROGRAMMATORE 15 CICLI 48x96 2AI+2AO+4DI+2DO+4RELE+RS485
FEATURES
| Dimensions | 48x96x88mm | 
|---|---|
| Power supply | 24..230V AC/DC ±15% 50/60 Hz - galvanic isolation 2,5KV | 
| Consumption | 7 Watt/VA | 
| Operating conditions | Temperature 0..45 °C, humidity 35..95 RH% (non-condensing), max 2000m a.s.l. | 
| Front panel | 48 x 96mm | 
| Material | Box: PC UL94V2 self-extinguishing, front panel: PC UL94V2 | 
| Weight | Circa 245g | 
| Sealing | Front panel: IP65, Box and terminal blocks: IP20 | 
| According to | CE, UL | 
| Analog inputs | 2x 16bit, K,S,R,J,T,E,N,B (comp. -25..85°C, Tol. @25°±0,2% F.S. ±1 digit F.S.), PT100, PT500, PT1000, Ni100, PTC 1K, NTC 10K (B3435K), 0..1/5/10V, 0-20/4..20mA, 0..60 mV, potentiometer 1..150KΩ | 
| Sampling time | Programmable up to 4,1ms (from 4,17Hz to 470Hz frequency) | 
| Digital outputs | 2 x PNP 12VDC - 30mA max | 
| Relais outputs | 4 x 5A - 250V AC resistive loads | 
| Analogue outputs | 2 x 4..20mA (40000 points ± 0,2% F.S.) or 0..10VDC (40000 points ± 0,2% F.S.) | 
| Control algorithms | ON - OFF with hysteresis, P., P.I., P.I.D., P.D. time proportional | 
| Tuning | Manual or automatic | 
| Alarm mode | Absolute / Threshold, Band, High / Low deviation. Alarm with optional Manual reset. Loop Break Alarm | 
| Double P.I.D. | Heating / Cooling with dual P.I.D. | 
| Software parameter configuration | Memory Card, software LABSOFTVIEW, EASY-UP codes | 
| Digital inputs | 4 x PNP | 
| Serial communication | RS485 (1200..115200 Baud) galvanically isolated | 
| Cycles / Profiles | up to 15 | 
| Steps / Segments | up to 30 for each cycle ( max duration per step 99.59 hh.mm) | 
 
                                                 
                                                 
                                                 
                                                 
                                                 
                             
                             
                             
                            